[SVE-641407876] Siemens SIMATIC, SIMOTION, and SINUMERIK

Date Type Platform Author EDB-ID CVE-ID OSVDB-ID Download App SIS Signature
2018-03-01OtherSiemensSiemens ProductCERT reported the vulnerabilities to NCCIC.N/ACVE-2017-5705 CVE-2017-5706 CVE-2017-5707 CVE-2017-5712 CVE-2017N/AN/AN/A

Source

						
							
								
#
# Siemens SIMATIC, SIMOTION, and SINUMERIK
#


### VULNERABLE VENDOR
Siemens


### VULNERABLE PRODUCT
SIMATIC, SIMOTION, and SINUMERIK 


### RESEARCHER
Siemens ProductCERT reported the vulnerabilities to NCCIC.


### AFFECTED PRODUCTS
Siemens reports that the vulnerabilities affect the following Industrial PCs and BIOS versions:

SIMATIC Field-PG M3: ME prior to V6.2.61.3535,
SIMATIC Field-PG M4: BIOS prior to V18.01.06,
SIMATIC Field-PG M5: BIOS prior to V22.01.04,
SIMATIC HMI IPC677C: ME prior to V6.2.61.3535,
SIMATIC IPC427D: BIOS prior to V17.0?.10,
SIMATIC IPC427E: BIOS prior to V21.01.07,
SIMATIC IPC477D: BIOS prior to V17.0?.10,
SIMATIC IPC477D PRO: BIOS prior to V17.0?.10,
SIMATIC IPC477E: BIOS prior to V21.01.07,
SIMATIC IPC547D: ME prior to V7.1.91.3272,
SIMATIC IPC547E: ME prior to V9.1.41.3024,
SIMATIC IPC547G: ME prior to V11.8.50.3425 and BIOS < R1.21.0,
SIMATIC IPC627C: ME prior to V6.2.61.3535,
SIMATIC IPC627D: ME prior to V9.1.41.3024,
SIMATIC IPC647C: ME prior to V6.2.61.3535,
SIMATIC IPC647D: ME prior to V9.1.41.3024,
SIMATIC IPC677D: ME prior to V9.1.41.3024,
SIMATIC IPC827C: ME prior to V6.2.61.3535,
SIMATIC IPC827D: ME prior to V9.1.41.3024,
SIMATIC IPC847C: ME prior to V6.2.61.3535,
SIMATIC IPC847D: ME prior to V9.1.41.3024,
SIMATIC ITP1000: BIOS prior to V23.01.03,
SINUMERIK PCU50.5-C, WIN7: ME prior to V6.2.61.3535,
SINUMERIK PCU50.5-C, WINXP: ME prior to V6.2.61.3535,
SINUMERIK PCU50.5-P, WIN7: ME prior to V6.2.61.3535,
SINUMERIK PCU50.5-P, WINXP: ME prior to V6.2.61.3535, and
SIMOTION P320-4S: BIOS < S17.02.06.83.1



### IMPACT
Successful exploitation of these vulnerabilities could result in execution of arbitrary code, extended privileges, and unauthenticated access to sensitive data.


### VULNERABILITY OVERVIEW
STACK-BASED BUFFER OVERFLOW CWE-121
Multiple buffer overflows could allow attackers to execute arbitrary code.
Local access to the system is required to exploit this vulnerability.
CVE-2017-5705, CVE-2017-5706, and CVE-2017-5707 have been assigned to these vulnerabilities.
A CVSS v3 base score of 8.2 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:H/UI:N/S:C/C:H/I:H/A:H)


STACK-BASED BUFFER OVERFLOW CWE-121
A buffer overflow could allow remote authenticated attackers to execute arbitrary code with extended privileges.
CVE-2017-5712 has been assigned to this vulnerability.
A CVSS v3 base score of 7.2 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H)


STACK-BASED BUFFER OVERFLOW CWE-121
Multiple buffer overflows could allow attackers with local access to execute arbitrary code.
CVE-2017-5711 has been assigned to this vulnerability.
A CVSS v3 base score of 6.7 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H)


PERMISSIONS, PRIVILEGES, AND ACCESS CONTROLS CWE-264
Multiple privilege escalations could allow unauthenticated access to sensitive data.
CVE-2017-5708, CVE-2017-5709, and CVE-2017-5710  have been assigned to these vulnerabilities.
A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:L/AC:H/PR:L/UI:N/S:C/C:H/I:H/A:N)





### BACKGROUND
Critical Infrastructure Sectors: Chemical, Critical Manufacturing, Energy, Food and Agriculture, Water and Wastewater Systems.
Countries/Areas Deployed: Worldwide
Company Headquarters Location: Germany




### MITIGATION

As a general security measure, Siemens strongly recommends protecting network access to devices with appropriate mechanisms. In order to run the devices in a protected IT environment, Siemens particularly recommends users configure the environment according to Siemens’ Operational Guidelines for Industrial Security, and follow the recommendations in the product manuals. The Operational Guidelines for Industrial Security can be found at:

https://www.siemens.com/cert/operational-guidelines-industrial-security


Additional information on Industrial Security by Siemens can be found at: 
https://www.siemens.com/global/en/home/company/topic-areas/future-of-manufacturing/industrial-security.html


Siemens has identified the following specific workarounds and mitigations users can apply to reduce the risk:

The attacker must have network access for CVE-2017-5712 and local access for all other vulnerabilities. Siemens recommends operating the devices only within trusted networks.

For more information on these vulnerabilities and associated software updates, please see Siemens security notification SSA-892715 on their website:

https://cert-portal.siemens.com/productcert/pdf/ssa-892715.pdf